Products

Protect your precious property with the best products

PS Series

PS Series

PS2 - Type 2/ Type 1CA
Pluggable Multi-Pole

PS2  - Type 2/ Type 1CA<br>Pluggable Multi-Pole
Applicable standard

• UL® 1449 4th Edition Type 2 and Type 1CA
• UL 1283 6th Edition
• CSA® (CSAT) Type 2 and Type 1CA
• RoHS compliant

Product Features

- Frequency (Hz) : 50/60
- Protection Mode : L-N / N-PE
- Degree of protection : IP 20
- Diagnostics : Green Flags (Protected) / Red Flags (Replace)
- Connection & Mounting Method : Parallel Connection Type / Wall Mounting
- Internal Disconnector : Thermal Runaway Multi-Fusing Protection
- Size of connecting wir : 4 ~ 6 mm2 (or # 11 ~ 9AWG)

Model No. PS2-40S PS2-40G PS2-40S2P PS2-40S/40G
Rated System Voltage
Single-Phase Single-Phase 2W
MCOV (Vac)
50 ~ 1000
In(kA)-8/20㎲- / Imax(kA)-8/20㎲-
20/40 20/40 20/40 20/40
VPR(Vpk)
L-N
- 1.5 - 1.5
N-PE
- 1.5 - 1.5
SCCR(kA)
200
Model No. PS2-40S3P PS2-40S3P/40G
Rated System Voltage
Tri-Phase 3W Tri-Phase 4W
MCOV (Vac)
50 ~ 1000
In(kA)-8/20㎲- / Imax(kA)-8/20㎲-
20/40 20/40
VPR(Vpk)
L-N
- 1.5
N-PE
1.5 1.5
SCCR(kA)
200
Optional Functions

- Remote Contact

Spec Sheets and Downloads
Installation diagram

Installation diagram

Installation & Circuit diagram

Installation & Circuit diagram

Installation & Circuit diagram

Dimensions (or Product size)
Dimensions (or Product size)
Circuit Diagram
Circuit Diagram

PS series DIN-rail SPD is type 1CA SPD according to UL 1449 4th designed for low-voltage power supply system surge protection, especially for point of entry and sub-circuit protection.
PS series features PrimePowerSolutions’s global patented fail-safe and self-protected technology, offering quick thermal response and perfect cut-off function and providing fast and reliable protection for various power supply systems.
Built with window fault indication and optional remote alarm contact, it can monitor the operating status of the SPD itself.

iconDownload Catalog